4-17
Group 06- Auto Run(Auto Sequencer) function
No. Description Range
Factory
Setting
Unit Note
06-34
Auto_ Run Mode
running direction 2
0 -
06-35
Auto_ Run Mode
running direction 3
0 -
06-36
Auto_ Run Mode
running direction 4
0 -
06-37
Auto_ Run Mode
running direction 5
0 -
06-38
Auto_ Run Mode
running direction 6
0 -
06-39
Auto_ Run Mode
running direction 7
0 -
Group 07- Start/Stop command setup
No. Description Range
Factory
Setting
Unit Note
07-00
Momentary Power
Loss and Restart
0: Momentary Power Loss and Restart disable
1: Momentary power loss and restart enable
0 s
07-01
Auto Restart Delay
Time
0.0~800.0
0.0 s
07-02
Number of Auto
Restart Attempts
0~10
0 -
07-03
Reset Mode Setting
0: Enable Reset Only when Run Command is
Off
1: Enable Reset when Run Command is On or
Off
0 -
07-04
Direct Running After
Power Up
0: Enable Direct run on power up
1: Disable Direct run on power up
1 -
07-05
Delay-ON Timer
1.0~300.0
1.0
s
07-06
DC Injection Brake
Start Frequency
(Hz) In Stop mode
0.10 ~ 10.00
1.5 Hz
07-07
DC Injection Brake
Level (%) In stop
mode
0 ~ 20 (Sizes 1/2). Based on the 20% of
maximum output voltage
5
%
0 ~ 100 (Sizes 3/4) based on the rated current
50
07-08
DC Injection Brake
Time (Seconds)
In stop mode
0.0 ~ 25.5
0.5 s
07-09
Stopping Method
0: Deceleration to stop
1: Coast to stop
0
07-10
DC Braking Level at
Start
0~100
0 %
07-11
DC Braking Time at
Start
0.0~25.5
0.0 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran BDI50 Series and is the answer not in the manual?

gefran BDI50 Series Specifications

General IconGeneral
Brandgefran
ModelBDI50 Series
CategoryInverter
LanguageEnglish

Related product manuals