4-28
(00-15)x(set frequency
-the minimum starting frequency
)
Actual acceleration time
=
(00-14)x(set frequency-the minimum starting frequency)
Motor rated frequency
Actual deceleration time=
Motor rated frequency
V/F Maximum output
Frequency or motor rated
frequency
Set frequency
Acc-time 00-14
Dec-time 00-15
Actual acc-time
Actual dec-time
Hz
T0
The minimum starting
frequency
V/F Maximum output frequency is for VF curve, which can be checked from table when VF curve is
fixed. Maximum output frequency is 01-02 when VF curve is customized, or motor rated frequency
02-06
Range
1.00~25.00
Hz
Range
0.1~25.5
s
Range
0.1~25.5
s
The JOG function is operational by using the multi-function input terminals S1 to S5 and setting
the relevant parameters 03-00~03-04 to 【6】JOG FWD or【7】JOG REV. Refer to parameter
group 3.