4-27
When 00-10=【0】,the initial frequency will be current frequency.
When 00-10=【1】,the initial frequency will be 0.
When 00-10=【2】,the initial frequency will be as set by parameter 00-11.
0.01~599.00
Hz
0.00~598.99
Hz
When 00-13 = 0 and frequency command is 0Hz, inverter output stays in zero speed.
When 00-13 > 0 and frequency command ≤ setting in 00-13, inverter output speed = setting in 00-13
Frequency upper limit
Frequency Lower limit
0
Hz
T
0.1~3600.0
s
0.1~3600.0
s
0.1~3600.0
s
0.1~3600.0
s
Preset Acceleration and Deceleration times by above parameters are the time taken for the output
frequency to ramp up or ramp down between the Upper and the lower V/F frequency limits.
Actual acceleration and deceleration time is calculated as follows:
V/F mode:
(00-
15)x
(set frequency-the minimum starting frequency)
Actual acceleration time=
(
00-14)x(set frequency-the minimum starting frequency)
V/F Maximum output frequency
Actual deceleration time=
V
/F Maximum output frequency
SLV mode: