4-37
1) For setting parameters 03- 00~03- 04 to
0, 1
External Run/Stop Control, refer to 00- 04.
2-wire method. Mode 1.
Example: FWD/STOP and REV/STOP from two inputs ( S1&S2)
Set 00- 04=
0
, S1: 03- 00=
0
(FWD/STOP) , S2: 03- 01=
1
(REV/STOP);
Note: If both forward and reverse commands are ON, it will be treated as a STOP.
2-wire method. Mode 2.
Example: RUN/STOP and REV/FWD from two inputs ( S1&S2)
Set 00- 04=
1
; S1: 03- 00=
0
(RUN/STOP); S2:03- 01=
1
(REV/FWD);
S1 ON OFF
FWD
REV
S2
T
Hz
ON
OFF
BDI50
S1
S2
COM
FWD/STOP
REV/STOP
BDI50
S1
S2
COM
RUN /STOP
REV/FWD