EasyManua.ls Logo

gefran GTF - Power Fault and HB Alarm Enablement; HB Alarm Setpoint Configuration

gefran GTF
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1580961F_MSW_GTF/GTF-Xtra_07-2018_ENG
Enable alarm
5
XB.T
R/W
Delay time for activation of HB alarm
10
The value must exceed the cycle time of the
output to which the HB alarm is associated.
0 ... 999 sec
3
Xb.f
R/W
HB alarm functions
0
Table of HB alarm functions
0
alarm active at a load current value below
set point for control output ON time.
1
alarm active at a load current value above
set point for control output OFF time.
2
Alarm active if one of functions 0 and 1 is active
(OR logic between functions 0 and 1) (*)
3 Continuous alarm
(*) minimum setpoint is set at 12% of ammeter full scale
+ 8 HB reverse alarm
+32 HB alarm with memory
43
hd.2
R/W
Enable POWER_FAULT alarms
0
Table of Power Fault alarms
SSR_SHORT NO_ VOLTAGE NO_CURRENT
0
1 x
2 x
3 x x
8 x
9 x x
10 x x
11 x x x
+ 32 with memory alarm
+64 for enabling HB alarm
Alarm setpoints
90,0
0
0,0 ... 100,0%
0...1
6
xb.P
R/W
Percentage HB alarm setpoint of
current read in HB calibration
14 bit
Calibration HB
alarm setpoint
for zone
R/W
OFF = Calibration not enabled
ON = Calibration enabled
10,0
L.tA ... H.tA A
4
A.xb
R/W
HB alarm setpoint (scale points
ammeter input)
Read state
0,09
xb.P
R/W
Ou.P power in HB calibration/
0,08
xb.t.
R/W TV read in HB calibration
7
xb.tA
R/W CT read in HB calibration
0,0
100,0
0,0 ... 100,0%
82
xb.P
R/W
Maximum limit with conduction HB
calibration (only for IR lamps)

Related product manuals