—————— Instruction manual ——————
149
Enable drive Whentheconverteriscontrolledviathekeypad,itisactivatedviatheEnable drive parameter.
Avoltageisalsorequiredonterminal12.TheStartcommandisrequiredforstarting
thedrive.
Enabled Enabledrive
Disable Drivedisabled
Start/Stop UsingthekeypadasStart/Stopcontrol,ifEkeyispushed,themotorrunatthespeedset.
Ramp red (d) Totalreferencevaluefortherampinunitsspeciedbythefactorfunction.
Ramp ref (rpm) Totalreferencevaluefortherampinrpm.
Ramp ref (%) TotalreferencevaluefortherampasapercentageoftheSpeed base value.
Ramp output (d) Rampoutputinunitsspeciedbythefactorfunction.
Ramp outp (rpm) Rampoutputinrpm.
Ramp output (%) RampoutputasapercentageoftheSpeed base value.
Speed ref (d) Totalspeedreferencevalueinunitsspeciedbythefactorfunction.
Speed ref (rpm) Totalspeedreferencevalueinrpm.
Speed ref (%) TotalspeedreferencevalueasapercentageoftheSpeed base value.
Actual spd (d) Actualspeedinunitsspeciedbythefactorfunction.
Actual spd (rpm) Actualspeedinrpm(revolutionsperminute).
Actual spd (%) ActualspeedasapercentageoftheSpeed base value.
F act spd (d) FilteredvalueofActual speed inunitsspeciedbythefactorfunction.
F act spd (rpm) FilteredvalueofActual speed inrpm.
Act spd lter1
st
orderlowpassltertimeconstantonActual speed.
Enc 1 speed (rpm) Actualspeedmeasuredbytheencoder1.Theparameterisaccessibleonlywhen
jumpersS5andS6areinpositionA.
Ifadigitalencoderisusedasencoder1,itmustbeinterfacedtotheconverterby
meansofcardDEII.
Enc. 2 speed (rpm) Actualspeedmeasuredbytheencoder2.
Mains voltage MainsvoltageinV.
Mains frequency ACinputfrequencyinHz.
Output power Outputpowervaluein Kw.
Output voltage ArmatureVoltageU
dA
inV
AV
Motor current Armaturecurrentin%ofFull load curr.
F T curr (%) FilteredvalueofTorque current inpercentage.
T curr lter 1
st
orderlowpassltertimeconstantonTorque current.
T current ref TotalcurrentreferencevalueasapercentageoftheFull load current.
Flux reference Fieldcurrent(reference)asapercentageof Motor nom ux.
Flux curr (%) Actualeldcurrentvalueaspercentageof Motor nom ux.
Flux curr (A) Actualeldcurrentvalueinamps.
Digital I/O StatusofthedigitalinputandoutputofthebaseconverterandthecardTBO.
Display: I12345678ESF
Q12345678
AnI/Oisdisplayedonlyifavoltageispresentonthecorrespondingterminal.E.g.,if
theinputs4and6aredisplayed,thatmeansthatthedigitalinputs4and6ontheTBO
cardaretoHighlevel.
E=Enabledrive(terminal12)
S=Start(terminal13)
F=Faststop(terminal14)
WhenaseriallineoraBusisused,thestatusofthedigitalI/Ocanbereadbymeans
oftheDig input termandDig output termparameters.