Alarm Ignore Warning Disable drive Quick stop Normal stop Curr lim stop
Bus loss
X X X X X X
SCR test
X X X - - -
Hw Opt 1 failure
- X X X X X
Enable seq err
X - X - - -
GD6165g
Latch ON Thealarmisstored.Theprogrammedactions(e.g.opening
theOKrelay)areenabled.Thisstatusiskeptlatchedevenif
thefaultconditionisrestored.AResetcommandisrequired
beforearestart.
OFF Incaseofalarm,thedriveisdisabledandtheprogrammed
functionsareenabled.Thealarmisnotlatched.Whenthe
failureisremoved,thealarmis automaticallyresetandthe
devicetriesrestarting.
Ok relay open ON Analarmcausestheopeningofthepotentialisolatedcontact
betweenterminals35and36.
OFF Thealarm doesnotcausetheopening ofthepotentialfree
contactoftheOKrelay.
Hold off time Delaytimebetweenthealarmconditiondetectionandthealarmactivation.Ifanalarm
conditionoccursthealarmstayOFFforthe Hold off time.Whenthistimeiselapsed
andthealarmisstillpresent,thealarmactivates.
Restart time IfLatch=Offandthealarmconditionpersistsevenafterthetimedenedvia Restart
time,thealarmisstoredandnorestartispossible(Latch=OFF).
note! InTerminalmodetoresetthefaulttheterminalsenableandstartmustbeatzerovoltage.The
occurrenceofafailureisindicatedinthedisplayofthekeypad.If“Latch”=ONisselected,
aResetcommandisnecessary.Thiscanbecarriedout,forexample,bypressingtheCANC
keyonthekeypad.Ifaseconderroroccursbeforetherstonewasreset,thetext“Multiple
failures”willappearinthedisplay.Inthiscase,aresetisonlypossibleviaFailure reset
parameterintheSPECFUNCTIONSmenu.TheresetcanbeobtainedbypressingtheE
keywithadisabledinverter.
Failure supply Failureonthesupplyvoltage.
Itindicatesafailureontheinternalvoltageoftheregulationcircuit.Themessage“Failure
supply”occursifanenabledconverterhasnovoltageontheU2andV2terminals.If
itisofashortdurationandrestored,apossibledigitaloutputpreparedforthemessage
issettoaLowcondition.Anormalresetcanbecarriedout.
Undervoltage ACInputundervoltage.
IncaseofanACInputvoltagewhentheregulationisenabled(Enable drive = Enabled)
themessageUndervoltageappears.Theconverterisimmediatelydisabled.Tothis
purposeaninterventionthresholdispresetviatheUndervolt thr parameter.
Ifthealarmisnotsaved(Latch=OFF),thedrivetriestostartautomaticallyafterthe
voltagehasbeenrestored.Usingtheramp,whenthevoltageisrestored,ifthefunction
Autocaptureisactive,therampoutputissettothevaluecorrespondingtothecurrent
motorspeed.Thisavoidsspeedjumps.
Overvoltage Armatureovervoltage.Thermessageappearswhenthearmaturevoltageexceedsthe
valuesetviaMax out voltageby20%.
Ifthealarmisnotsaved(Latch=OFF),thedrivewillattempttorestartautomatically
afterthevoltagehasbeenrestored.
Usingtheramp,whenthevoltageisrestored,ifthefunctionAutocaptureisactive,the
rampoutputissettothevaluecorrespondingtothecurrentmotorspeed.Thisavoids
speedjumps.
Overspeed ThisalarmconditionissignalledifthespeedlimitsetintheOverspeed thrparameter
isexceeded.