(3)Timermode3(OFF-delayTimermode1)
6
Timer start
OFF
OFF
5
OFF
OFF
When the set value is reached, the
timer output turns on (T1 to T8)
4
Timer reset
Internal timer value = 0
3
Internal timer value
Reset internal
timer value
and output
T= timer set value
ON
OFFOFF
Reset timer and output
ON
T
6
Timer start
OFF
OFF
OFF
OFF
When the set value is reached, the
timer output turns on (T1 to T8)
3
T= timer set value
ON
OFFOFF
Reset timer and output
ON
T
ON ON
ON
T OFF
ON
OFF
T
(4)Timermode4(OFF-delayTimermode2)
Timer start
T
OFF
OFF
ON
OFF
OFF
When the set value is reached, the
timer output turns on (T1 to T8)
Timer reset
Internal timer value = 0
Internal timer value
T= timer set value
ON
OFF
Reset timer and output
Reset internal
timer value and
output
(5)Timermode5(FLASHTimermode1)
Timer start
When the set value is reached, the
timer output turns on (T1 to T8)
Timer reset
Internal timer value = 0
Present timing value
starts change for timing
T= timer set value
T T T T
Reset internal
timer value and
output
(6)Timermode6(FLASHTimermode2)
Timer start
When the set value is reached
the output point (T1 to T8)
Timer reset
Internal timer value = 0
Internal timer value
T= timer set value
T T T T
Reset timer and output
Reset internal
timer value and
output
(7)Timermode7(FLASHTimermode3)
Timer start
When the set value is reached, the
timer output turns on (T1 to T8)
Timer reset
Internal timer value = 0
Internal timer value
t1 t2
Reset internal timer
value and output
VDI100 • Instruction manual 291