32 / 48
1435
e
Pos
11.3.5 Setting position feedback function and limiting values
Position Output:
Submenu for setting the actual value output
Analog Out:
Determines the function of the actual value output.
0-10 V
0-20 mA (only available on version with optional current output)
4-20 mA (only available on version with optional current output)
Out min:
Defi nes the valve position at which an output signal of 0 V (0/4 mA) is emitted.
Out max:
Defi nes the valve position at which an output signal of 10 V (20 mA) is emitted.
11.3.6 Storing parameter sets
CpyParaSet:
The current positioner settings can be copied and read out in diff erent memories.
(P1<=W) Write from W to P1
(P1=>P2) Write from P1 to P2
(P1<=P2) Read from P2 to P1
(P1=>P3) Write from P1 to P3
(P1<=P3) Read from P3 to P1
(P1=>P4) Write from P1 to P4
(P1<=P4) Read from P4 to P1
(OFF) Storage function deactivated
P1: Memory 1
P2: Memory 2
P3: Memory 3
P4: Memory 4
W: Factory setting
The GEMÜ 1435 ePos automatically stores all parameters in working memory P1.