Maintenance
24 Synergy Automatic Standby Generator Owner’s Manual
4.4 — Remove From Service
To ensure safety, follow the steps below prior to inspection, maintenance or service.
1.
Unlock left and right side locks. Open lid.
NOTE: For best results, press down on lid directly above each side lock, and while holding the lid down, use
key to unlock latches.
2.
Press OFF on the control pad. A red LED illuminates to confirm that the system is in the OFF mode.
3.
Move the Generator Disconnect Circuit Breaker switch to the OFF (Open) position.
4.
If the generator has been running, allow one hour to elapse for unit to cool down and fans to stop running.
5.
Pull up rubber flap covering fuse holder and remove 7.5 amp fuse.
6.
Remove T1 fuse from transfer switch.
4.5 — Daily Maintenance (If Running Continuously)
4.5.1— Check Enclosure Louvers
1.
Verify that intake and exhaust louvers and openings are clean and unobstructed.
2.
Wipe exterior surfaces clean using a damp cloth.
3.
Loosen dirt, oil, etc. with a soft bristle brush.
4.
Remove loose dirt and debris using a vacuum cleaner, or low pressure compressed air (not exceeding 25 psi).
NOTE: Periodically wash and wax enclosure using automotive type products. Frequent washing is recom-
mended in salt water/coastal areas.
Table 4-1. Service Maintenance Schedule
Service
Daily If Running
Continuously
or
Before Each Use
Every
Year
Schedule A
Every
Two Years
or 200 Hours
Schedule B
Every
Four Years
or 400 Hours
Check Enclosure Louvers
for Dirt and Debris
Check Lines and Connections for
Fuel or Oil Leaks
Check Engine Oil Level
Check Battery Condition, Electrolyte
Level, and State of Charge
Replace AVR Filter *
Replace Engine Oil and Oil Filter **
Replace Engine Air Filter
Replace/Gap Spark Plugs
Inspect/Adjust Valve Clearance ***
Contact the nearest independent Authorized Service Dealer for assistance if necessary.
* Replace AVR filter more frequently if operating in dusty conditions.
** Change engine oil and filter after the first 25 hours of operation. In cold weather conditions (ambient below 40
º
F/ 4.4
º
C),
or if unit is operated continuously in hot weather conditions (ambient above 85
º
F / 29.4
º
C), change engine oil and filter
every year or 100 hours of operation.
*** Check/adjust valve clearance after the first 25 hours of operation.