vii
Work Modes
GV-AS200 and GV-AS400 Controllers support the four types of Work Modes for door-
access control. By default GV-AS Controller is set to one-way control.
One-way control: A door is equipped with one card reader for entry. For example, a
user may swipe a card to open the door of office and push a button to leave from the
same door.
Two-way control: A door is equipped with two card readers. The outer reader is
defined as entry reader and the inner reader is defined as exit reader. For example, a
user may swipe a card to gain access to a laboratory, and swipe a card to exit from the
same door.
Mixed control: A mix of One-Way and Two-Way Control applications. Some doors are
equipped with one card reader for entry and some doors are equipped with two card
readers for entry and exit. For example, a building includes both office and laboratory
applications.
One-way traffic: Two doors are applied for entry and exit separately. For example, in a
parking lot, a user may swipe a card at the entrance and swipe a card again at the exit.
Installation Considerations
1. There are distance limitations for Wiegand and RS-485 communications. Please note:
Wiegand interface: 30 meters (98.43 feet)
RS-485 interface: 600 meters (1968.50 feet)
Recommended cable: standard 485 cable (a twisted pair of 24 AWG wires)
2. GV-ASManager software is used to manage GV-AS100/GV-AS200/GV-AS400 Controllers.
There is a limit for the number of controllers connected to GV-ASManager based on
communication modes.
Through the network, up to 255 GV-AS100/GV-AS200/GV-AS400 Controllers can
connect to GV-ASManager.
Through RS-485 connection, up to 16 GV-AS100/GV-AS200/GV-AS400 Controllers
can connect to the same COM port on a computer running GV-ASManager.

Table of Contents

Other manuals for GeoVision GV-AS100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GeoVision GV-AS100 and is the answer not in the manual?

GeoVision GV-AS100 Specifications

General IconGeneral
InterfaceRS-485
Case designHousing
Built-in UPS-
Number of users40000 user(s)
Maximum number of doors1 door(s)
Number of Wiegand readers supported1
Power consumption200 mA
Operating temperature (T-T)0 - 65 °C
Operating relative humidity (H-H)10 - 90 %
Weight and Dimensions IconWeight and Dimensions
Depth27 mm
Width96 mm
Height137 mm
Weight250 g

Related product manuals