3.2. Space needed for use and maintenance
The
e
-Brick requires little maintenance following installation but clearance is required to allow
adequate cooling of the internal electronics.
Allow the following clearances (see Figure 5):
>500mm from the air intake
>300mm from the exhaust outlet
>25mm from sides
If the
e
-Brick will be mounted in an enclosure rather than in free air, it is essential that adequate
ventilation is provided. Refer to Table 2 for the rated power dissipation for each product variant;
this figure should be taken in to account when calculating overall system cooling requirements.
e
-Brick variant Power dissipation (W)
9kW 475
12kW 900
22kW 1400
Table 2: Power dissipation
Figure 5: Installation clearances
GEW UV
e
-Brick installation and operating manual 14 of 49