0020107233_00 - 06/11 - Glow-worm
INSTALLATION
- 11 -
Diagram 4.2
A
directly below an opening, air brick,
opening windows
300
B above an opening, air brick, opening windows 300
C
horizontally to an opening, air brick, opening
windows
300
D below gutter, drain/soil pipe 25
E below eaves 25
(1)
F below a balcony or car port 25
G from vertical drain pipes and soil pipes 25
H from internal/external corners 25
H
(2)
to a boundary alongside the terminal 300
I above adjacent ground or balcony level 300
J
(2)
from surface or a boundary facing the terminal 600
L
from opening (door/window) in car port
into dwelling
1200
M vertical from a terminal 1500
N horizontally from a terminal 300
P from another terminal 600
Q above roof level 300
R from adjacent opening window 1000
S from adjacent wall to ue 300
(1) There should be no ventilation/opening in the eaves within
300mm distance of the terminal.
(2) These dimensions comply with the building regulations,
but they may need to be increased to avoid wall staining and
nuisance from pluming depending on site conditions.