6 Set-up
18 Installation and maintenance instructions Energy
7
0020300877_01
6.6.4 Flue Configuration Description
6.6.4.1 Horizontal Concentric Flue 60/100 mm or
80/125 mm (C13 type installation)
1
1 Gasket (fitted)
Note
If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection kit.
Type Max. length (L) Height (H)
60/100 diameter
10 m 76 mm
80/125 diameter
25 m 169 mm
Each time an additional 90° bend is necessary (or 2 at 45°),
the length (L) must be reduced by 1 m.
6.6.4.2 Vertical Concentric Flue 60/100 mm or
80/125 mm (C33 type installation)
Consult the separate installation manual for air/flue gas sys-
tems supplied with your appliance for all possibilities and as-
sociated accessories and how to install the flue system.