C Overview of diagnostics codes
Setting level Values
Unit Increment, select, explanation
Default set-
ting
Own setting
Min. Max.
d.00 Heating maximum output kW The maximum heating output varies
depending on the product.
Section "Technical data"
Section
"Technical
data"
Adjustable
d.01 Pump overrun time in
heating mode
1 60 min 1 5 Adjustable
d.02 Burner anti-cycling time
in heating mode
2 60 min 1 20 Adjustable
d.04 Water temperature in the
cylinder
Current value Not
adjustable
d.05 Determined target heating
flow temperature
Current value
Not
adjustable
d.07 Target temperature for
the domestic hot water cylin-
der
Current value Not
adjustable
d.08 Status of the 230 V ther-
mostat
Current value 0 = Room thermostat open (no heat
requirement)
1 = Room thermostat closed (heat
requirement)
Not
adjustable
d.09 Target heating flow tem-
perature that is set on the
eBUS room thermostat
Current value Not
adjustable
d.10 Status of the internal
pump in the heating circuit
Current value off / on Not
adjustable
d.11 Status of the heating cir-
cuit's shunt pump
Current value off / on Not
adjustable
d.13 Status of the domestic
hot water circuit's circulation
pump
Current value off / on Not
adjustable
d.16 Status of the 24 V room
thermostat
Current value off = Heating off
on = Heating on
Not
adjustable
d.17 Heating control off = Flow temperature
on = Return temperature (adjustment
for underfloor heating. If you have ac-
tivated the return temperature control,
the automatic heating output determ-
ination function is not active.)
0 Adjustable
d.18 Pump overrun operating
mode
1 3 1 = Comfort (continuously operating
pump)
3 = Eco (intermittent pump operation
for the dissipation of the residual
heat after domestic hot water gen-
eration at an extremely low heat de-
mand)
1 Adjustable
d.20 Maximum target domestic
hot water temperature
50 60 1 50 Adjustable
d.23 Status of the heat de-
mand
Current value off = Heating off (Summer mode)
on = Heating on
Not
adjustable
d.24 Status of the pressure
switch
0 1 off = Not switched
on = Switched
Not
adjustable
d.25 Status of the requirement
to reheat the cylinder or for
the domestic hot water warm
start from the eBUS thermo-
stat
Current value off = Function deactivated
on = Function activated
Not
adjustable