EasyManuals Logo

Go Power GP-BMK-50 User Manual

Go Power GP-BMK-50
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
[page 20] | gpelectric.com
40. Clear Low Starter Voltage Alarm
When the auxiliary voltage rises above this value, the alarm is switched o󰀨. This value needs to be greater than or
equal to the previous parameter.
41. High Starter Voltage Alarm
When the auxiliary (e.g. starter battery) voltage rises above this value for more than 10 seconds, the alarm will be
activated. This is a visual and audible alarm. It does not energize the relay.
42. Clear High Starter Voltage Alarm
When the auxiliary voltage falls below this value, the alarm is switched o󰀨. This value needs to be less than or equal
to the previous parameter.
Default Range Step Size
OV 0-95V 0.1 V
43. High Temperature Alarm
When the battery temperature rises above this value for more than 10 seconds, the alarm will be activated. This is
a visual and audible alarm. It does not energize the relay.
44. Clear High Temperature Alarm
When the temperature falls below this value, the alarm is switched o󰀨. This value needs to be less than or equal to
the previous parameter.
45. Low Temperature Alarm
When the temperature falls below this value for more than 10 seconds, the alarm will be activated. This is a visual
and audible alarm. It does not energize the relay.
46. Clear Low Temperature Alarm
When the temperature rises above this value, the alarm is switched o󰀨. This value needs to be greater than or equal
to the previous parameter. See parameter 67 for choosing between °C and °F.
Default Range Step Size
0°C -99 - 99°C 1°C
0°F -146 - 210°F 1°F
47. Mid Voltage Alarm
When the mid-point voltage deviation rises above this value for more than 10 seconds, the alarm will be activated.
This is a visual and audible alarm. It does not energize the relay. See section 5.2 for more information about midpoint
voltage.
Default Range Step Size
2% 0-99% 0.1%
FULL SET-UP DETAILS

Other manuals for Go Power GP-BMK-50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Go Power GP-BMK-50 and is the answer not in the manual?

Go Power GP-BMK-50 Specifications

General IconGeneral
BrandGo Power
ModelGP-BMK-50
CategoryMonitor
LanguageEnglish

Related product manuals