EasyManua.ls Logo

Goodwe SDT G2 Series - Routine Maintenance

Goodwe SDT G2 Series
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
User Manual V1.0-2022-01-17
09 Maintenance
9.5 Routine Maintenance
Maintaining Item Maintaining Method Maintaining Period
System Clean
Check the heat sink, air intake, and air
outlet for foreign matter or dust.
Once 6-12 months
Fan
Check the fan for proper working status,
low noise, and intact appearance.
Once a year
DC Switch
Turn the DC switch on and o󽗈 ten
consecutive times to make sure that it is
working properly.
Once a year
Electrical
Connection
Check whether the cables are securely
connected. Check whether the cables are
broken, or whether there is any exposed
copper core.
Once 6-12 months
Sealing
Check whether all the terminals and ports
are properly sealed. Reseal the cable hole
if it is not sealed or too big.
Once a year
THDi Test
For Australia requirements, in the THDi
test, there should add Zref between
inverter and mains.
Zref:
Zmax or Zref (phase current>16A)
Zref: L: 0.24 Ω + j0.15 Ω; N: 0.16 Ω + j0.10 Ω
(phase current>16A, <21.7A)
Zref: L: 0.15 Ω + j0.15 Ω; N: 0.1 Ω + j0.1 Ω
(phase current>21.7A, <75A)
Zref: ≥5% Un/Irated+j5% Un/Irated (phase
current>75A)
As needed

Other manuals for Goodwe SDT G2 Series

Related product manuals