Troubleshooting
3A9522A 13
Weak or no RF signal Changes or obstructions in RF
pathway (i.e., vehicles, overhead
doors, etc.)
Add Graco Extender to Pulse
System. Order Graco Part No.
17F885 - US/Canada; 17F886 -
EU; 17F887 - UK; 17F888 - ANZ.
Weak or dead batteries Replace batteries. See Replace
the Batteries, page 14.
Monitor readings are inaccurate. Tank geometry incorrectly
defined.
See Tank Level Monitor Soft-
ware Guide or PC Software
Guide for details -
http://setup.gracopulse.com
TLM has not been updated with
latest adjustments made within
The profile ID on the Pulse sys-
tem.
Manually push DISPLAY button
on TLM.
Fluid surface is moving while
reading is being taken.
Ensure the pump is not operat-
ing and nothing is disturbing the
surface of the fluid during read-
ings.
Pipe adapters installed in the
tank bung.
Ensure there are no adapters
installed in the tank bung.
TLM is not perpendicular to top
of fluid.
Level tank so that it is perpen-
dicular to top of the fluid and/or
realign TLM.
Inside tank obstruction. Install in different tank bung to
avoid tank obstruction.
Device is unable to register to
the Pulse Pro network or the
device does not rejoin the net-
work after system reboot. .
Device is not meshing properly
with the device network.
Toggle to Discovery mode on
the HUB. Wait one minute and
toggle it back. Press the button
to attempt a network connec-
tion. If this does not resolve the
issue, remove the batteries, wait
two minutes then reinstall the
batteries.
Problem Cause Solution