EasyManua.ls Logo

Gree FP-22LM/D-K - Capacity Correction

Gree FP-22LM/D-K
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Product
1.5.3 Capacity correction
(1) Cooling and heating capacity correction factor
Model
FP-22 FP-34 FP-51 FP-68 FP-85 FP-102 FP-119 FP-136 FP-170 FP-204
Middle
speed
Cooling
0.81 0.82 0.75 0.71 0.72 0.73 0.74 0.79 0.76 0.77
Heating
0.80 0.80 0.73 0.68 0.69 0.70 0.72 0.78 0.74 0.72
Low
speed
Cooling
0.67 0.65 0.59 0.55 0.63 0.52 0.66 0.63 0.62 0.59
Heating
0.63 0.62 0.56 0.52 0.60 0.50 0.63 0.60 0.60 0.57
(2) Cooling capacity correction factor
Entering
water
temp. (°C)
Water
ow
(multiple)
Inlet air
DB24°C DB25°C DB26°C DB27°C DB28°C
WB17°C WB18°C WB19°C WB19.5°C WB21°C
SH TH SH TH SH TH SH TH SH TH
5
0.8 0.70 0.80 0.73 0.88 0.75 0.97 0.79 1.02 0.80 1.16
1.0 0.74 0.89 0.78 0.98 0.79 1.07 0.84 1.13 0.84 1.29
1.2 0.77 0.96 0.80 1.05 0.82 1.15 0.87 1.21 0.87 1.38
6
0.8 0.67 0.76 0.71 0.84 0.72 0.91 0.76 0.96 0.77 1.10
1.0 0.72 0.85 0.75 0.93 0.76 1.02 0.80 1.07 0.81 1.22
1.2 0.74 0.90 0.77 1.00 0.79 1.09 0.83 1.14 0.84 1.31
7
0.8 0.66 0.71 0.68 0.78 0.70 0.86 0.74 0.90 0.74 1.03
1.0 0.70 0.79 0.73 0.87 0.74 0.95 0.78 1.00 0.79 1.14
1.2 0.72 0.85 0.75 0.93 0.77 1.02 0.81 1.07 0.82 1.22
8
0.8 0.61 0.69 0.64 0.76 0.65 0.83 0.68 0.87 0.69 1.05
1.0 0.65 0.77 0.68 0.84 0.69 0.92 0.73 0.97 0.73 1.11
1.2 0.67 0.82 0.70 0.90 0.71 0.99 0.75 1.04 0.76 1.18
9
0.8 0.61 0.62 0.64 0.68 0.65 0.74 0.68 0.78 0.69 0.89
1.0 0.65 0.69 0.68 0.76 0.69 0.83 0.73 0.87 0.73 0.99
1.2 0.67 0.74 0.70 0.81 0.71 0.88 0.75 0.93 0.76 1.06
Notes:
(a) TH: total heat (W)
(b) SH: sensible heat (W)
(c) DB: dry bulb temperature (°C)
(d) WB: wet bulb temperature (°C)