PRODUCT
20
Package
dimension
(W×H)
Body
mm
960×960×257
960×960×257
960×960×310
960×960×394
Panel TB03
mm
1033×1038×133
1033×1038×133
1033×1038×133
1033×1038×133
Net weight
Body
kg
25.0
25.0
27.0
32.0
Panel TB03
kg
7
7
7
7
Gross
weight
Body
kg
33.0
33.0
34.0
41.0
Panel TB03
kg
11
11
11
11
Loading
quantity
20'GP (with panel TB03)
56
56
50
42
40'GP (with panel TB03)
131
131
121
98
40'HQ (with panel TB03)
147
147
134
112
Testing condition:
For 60Hz :
The FCU designed for installation indoor. The environmental temperature is fromC to 43°C, water
working temperature is fromC to 60°C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
(a) Cooling capacity: air 27°C DB, 19.5°C WB, water temperature: intake 7°C, outlet12°C.
(b) Heating capacity: air 21°C DB, Water temperature intake 60°C, the water-flow volume is same as
Cooling capacity .
(c) Freeze-up : air 27°C DB, 24°C WB, water temperature intake 6°C, outlet 9°C.
(d) Sound power level according to ISO 5151. Sound pressure level are calculated at the below of
air-outlet 1m and 1m distance. The noise are tested before leaving factory.
For 50 Hz :
The FCU designed for installation indoor. The environmental temperature is fromC to 43°C, water
working temperature is fromC to 60°C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing
conditions as below:
(a) Cooling capacity: air 27°C DB , 19°C WB, water temperature intake 7°C, outlet 12°C.
(b) Heating capacity: air 20°C DB , Water temperature intake 5C, outlet 40°C.
(c) Freeze-up : air 27°C DB, 24°C WB , water temperature C intake , 10°C outlet .
(d) Sound power level according to ISO 5151. Sound pressure level are calculated at the below of
air-outlet 1m and 1m distance. The noise are tested before leaving factory.
For 4 pipes:
The FCU designed for installation indoor. The environmental temperature is from C to 43°C, water
working temperature is fromC to 70°C.
The temperature exchange efficiency and enthalpy exchange efficiency are tested under these testing