25
Parameter
code
Parameter name
Parameter
range
Default
value
Note
P11
Set infrared
receiver of
wired controller
00: forbidden
01: activated
01
P13
Set address of
wired controller
01: master
wired controller
02: slave wired
controller
01
Assistant wired
controller (02) is
without unit
parameter
setting function except
setting its address.
P14
Set quantity of
group control
indoor units
00: forbid this
function
01-16: indoor
unit quantity
01
Set the corresponding
value according to the
connected indoor unit
quantity.