EasyManuals Logo

Greenheck DFD Series User Manual

Greenheck DFD Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Securing the Damper/Sleeve Assembly to Wall/Floor Openings cont.......
Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm])
Retaining angles used in conjunction with grille installations must be a minimum of
5
8 in. x 1 in. (15mm x 25mm)
16 gauge (1.5mm) steel. Space screws a maximum of 6 in. (152mm) O.C. and a maximum of 2 in. (51mm) from the
corners (minimum of 2 screws per side). See Figure 12 and Figure 13.
Note: Screws used to attach grille are allowed to penetrate reversed angle leg.
Damper
Sleeve
Angle Fastener
Grille (supplied
by others)
#10 sheet metal screws
spaced 6 in. on center
and a maximum of 2 in.
from the corners
(minimum of 2 screws per
side). Screw into studs so
as to avoid space
conflicts with the grille
Stud or Runner
Retaining Angle/Flange
Two layers of 1/2 in.
UL Classified Gypsum
Wallboard for 2 hour
rated walls. One layer
for 1 hour rated walls
(see UL Rated Wall
Design for Additional
Details).
Figure 13: Metal Stud - Grille
Two layers of 1/2 in. UL
Classified Gypsum
Wallboard for 2 hour
rated walls. One layer for
1 hour rated walls (see
UL Rated Wall Design for
Additional Details).
Grille (supplied by others)
Retaining Angle
Angle Fastener
Damper Sleeve
#10 sheet metal screws, 2
1/2 inches long, spaced 6
in. on center and a
maximum of 2 in. from the
corners (minimum of 2
screws per side). Screw
into studs so as to avoid
space conflicts with the
grille.
2 1/2 in. minimum
Stud or Runner
Figure 12: Wood Stud - Grille
Figure 14: Damper/Sleeves with Transition
Factory or Field installed Sleeve
1/4 in. minimum
total clearance
Wall or Floor
Maximum
6 in.
Maximum
6 in.
Duct
Duct
Duct
Damper
Damper
Damper
Wall or Floor
Wall or Floor
Retaining Angles
Type A
Type B
On types R, CO & CR factory
furnished duct collar
qualifies as breakaway
connection.
Type C, CO, CR, & R
Factory Sleeve
Wall or
Floor
Retaining Angles
Sleeve
Duct
“K” side
Damper
Max. 6 in.
Max. 6 in.
Type B
Factory Sleeve
1/4 in. minimum
total clearance
Wall or Floor
Maximum
6 in.
Maximum
6 in.
Duct
Duct
Duct
Damper
Damper
Damper
Wall or Floor
Wall or Floor
Retaining Angles
Type A
Type B
On types R, CO & CR factory
furnished duct collar
qualifies as breakaway
connection.
Type C, CO, CR, & R
Factory Sleeve
Type B2
Wall or floor
Damper
Sleeve
Field Installed Sleeve
Damper
1/4 in. minimum
total clearance
(See Section 1)
Maximum
6 in.
Maximum
6 in.
Wall or floor
Wall or floor
Wall or floor
Damper
Damper
Duct
Duct
Duct
Retaining Angles
(See Section 4)
Sleeve
(See Sleeve Requirements)
Sleeve
Sleeve
On types R & CR factory
furnished duct collar
qualifies as breakaway
connection (See Connecting
Ducts to Fire Damper Sleeve)
1 in. min.
overlap
Four sides
Mounting Angles
(See Para. 4)
1/4 in. minimum
total clearance
(See Para. 1)
Retaining angle leg
shall not exceed 7 in.
(178mm)
Type A
Type B
Type C, CO, CR & R
Field installed Sleeve
Damper
1/4 in. minimum
total clearance
(See Section 1)
Maximum
6 in.
Maximum
6 in.
Wall or floor
Wall or floor
Wall or floor
Damper
Damper
Duct
Duct
Duct
Retaining Angles
(See Section 4)
Sleeve
(See Sleeve Requirements)
Sleeve
Sleeve
On types R & CR factory
furnished duct collar
qualifies as breakaway
connection (See Connecting
Ducts to Fire Damper Sleeve)
1 in. min.
overlap
Four sides
Mounting Angles
(See Para. 4)
1/4 in. minimum
total clearance
(See Para. 1)
Retaining angle leg
shall not exceed 7 in.
(178mm)
Type A
Type B
Type C, CO, CR & R
8
Curtain Fire Dampers

Table of Contents

Other manuals for Greenheck DFD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Greenheck DFD Series and is the answer not in the manual?

Greenheck DFD Series Specifications

General IconGeneral
BrandGreenheck
ModelDFD Series
CategoryFire and Smoke Dampers
LanguageEnglish

Related product manuals