EasyManuals Logo

Greenheck DFD Series User Manual

Greenheck DFD Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
Securing the Damper/Sleeve Assembly to Wall/Floor Openings
All fire and combination fire smoke dampers may utilize the two sided angle installation method described below.
1
1
2 hour rated fire and combination fire smoke dampers may use the single sided angle installation method up to the
following maximum sizes:
Vertical mount: 80 in. W x 50. in. H (2032mm W x 1270mm H), 50 in. W x 80 in. H
(1270mm W x 2032mm H), or 40 in. W x 100 in. H (1016mm W x 2540mm).
Horizontal mount: 144 in. W x 96 in. H (3658mm W x 2438mm H)
Retaining Angle Gauge: Retaining angles for 1½ hour rated dampers with a width and height 48 in. (1219mm)
or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a
width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm).
Retaining Angle Size: The leg of the retaining angle on the damper sleeve shall be a minimum of 1¼ in. (32mm).
The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm).
Retaining Angle Attachment to Sleeve: Retaining angles must be attached to the damper using one or more of
the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
- Tack or spot welds
- #10 (
3
4 in. [19mm] max.) sheet metal screws
-
1
4 in. (6mm) bolts and nuts
-
3
16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom, spaced 12 in. (305mm) O.C. maximum are required for
openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers greater than 48 in. wide (1219mm) or 36 in.
high (914mm) require the connections to be no more than 6 in. (152mm) O.C..
The angles must be attached to all 4 sides of the sleeve. Ensure that fasteners do not interfere with the operation of
the damper. The angles need not be attached to each other at the corners.
• Retaining Angle Attachment to Wall/Floor:
Two-Sided Angle Method: For two-sided angle installations the
retaining angles shall not be attached to the wall/floor (see
Figure 9).
Single Sided Angle Method: For single side installations the
retaining angles must be attached to the wall/floor
(see Figures 10-13). For metal stud partitions only, the single side
mounting angle may be directly attached to the metal stud prior to
the installation of the drywall.
Retaining angles must be attached to the partition using one
of the methods shown below:
- Drywall screws of a length such that the screw
engages the steel stud/track by ½ in. (13mm) (steel
framing).
- Drywall screws of a length such that the screw
engages the wood stud by 1¾ in. (44mm) (wood
framing).
- Steel anchors or self tapping concrete screws penetrating masonry or block 1¼ in. (31mm).
A minimum of two connections per side are required. Additional connections made at a maximum
of 12 in. (305mm) O.C. for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less. Dampers
greater than 48 in. wide (1219mm) or 36 in. high (914mm) require the connections to be no more than
6 in. (152mm) O.C.
2 in. M ax.
6 in. M ax.
Sleeve
Retaining
Angle
Damper
Duct
Min. 1 in.
Overlap*
Wall or
Floor
Retaining
Angle
*only applicable for damper sizes above 36 in. x 36 in.
6 in. M ax.
2 in. M ax.
Figure 9: Two-sided angle
installation method
Multi-Blade Fire and Combination Fire Smoke Dampers 7

Table of Contents

Other manuals for Greenheck DFD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Greenheck DFD Series and is the answer not in the manual?

Greenheck DFD Series Specifications

General IconGeneral
BrandGreenheck
ModelDFD Series
CategoryFire and Smoke Dampers
LanguageEnglish

Related product manuals