EasyManua.ls Logo

Growatt 8000MTL-S - 6.3 Connecting the second protective conductor

Growatt 8000MTL-S
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
Wire suggestion length
Conductor cross
section
Max. cable length
Growatt 7000MTL-S
Growatt 8000MTL-S
10AWG
46m
40m
8AWG
70m
60m
6.3 Connecting the second protective conductor
If the installation requires,the ground terminal can be used to connect a second
protective conductor or as a equipotential bonding.The second protective point is
shown below.

Table of Contents