EasyManuals Logo
Home>Growatt>Inverter>SPF 18KT DVM-MPV

Growatt SPF 18KT DVM-MPV User Manual

Growatt SPF 18KT DVM-MPV
31 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
23
battery at the same time.
22
RS485
communication address
Default 001,001-255 settable
27
Battery equalization
Battery equalization disable
(default)
Battery equalization enable
If Flooded or User-Defined is selected in program 05, this program
can be set up.
28
Battery equalization
voltage
48V model: Default 58.4V, 48.0V~60V Settable (the value should be
higher than Program 19 value)
29
Battery equalized time
Default 60min, 5min~900min Settable
30
Battery equalized
timeout
Default 120min, 5min~900min Settable
31
Equalization interval
Default 1days, 1 days~90 days Settable
32
Equalization activated
immediately
Equalization activated immediately
enable
Equalization activated immediately disable (default)
If equalization function is enabled in program 27, this program can
be setup. If “On” is selected in this program, it’s to activate battery
equalization immediately and LCD main page will shows “ ”. If
Off” is selected, it will cancel equalization function until next
activated equalization time arrives based on program 31setting. At
this time, “ ” will not be shown in LCD main page.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF 18KT DVM-MPV and is the answer not in the manual?

Growatt SPF 18KT DVM-MPV Specifications

General IconGeneral
BrandGrowatt
ModelSPF 18KT DVM-MPV
CategoryInverter
LanguageEnglish

Related product manuals