battery at the same time.
RS485
communication address
Default 001,001-255 settable
Battery equalization disable
(default)
Battery equalization enable
If “Flooded” or “User-Defined” is selected in program 05, this program
can be set up.
Battery equalization
voltage
48V model: Default 58.4V, 48.0V~60V Settable (the value should be
higher than Program 19 value)
Default 60min, 5min~900min Settable
Battery equalized
timeout
Default 120min, 5min~900min Settable
Default 1days, 1 days~90 days Settable
Equalization activated
immediately
Equalization activated immediately
enable
Equalization activated immediately disable (default)
If equalization function is enabled in program 27, this program can
be setup. If “On” is selected in this program, it’s to activate battery
equalization immediately and LCD main page will shows “ ”. If
“Off” is selected, it will cancel equalization function until next
activated equalization time arrives based on program 31setting. At
this time, “ ” will not be shown in LCD main page.