Page #21 background imageLoading...
Page #21 background image
19
12
Setting voltage point back
to utility source when
selecting “SBU priority or
“Solar first” in program 01
Default 46.0V, 44.0V~51.2V Settable
Default 40%, 6%~50% Settable, value set higher than Program 21 setting
13
Setting voltage point back
to battery mode when
selecting “SBU priority
or “Solar first in program
01
Default 54.0V, 48.0V~58.0V Settable
Lithium battery mode: default 80%, 60%~100% settable
14
Charger source priority:
To configure charger
source priority
If this off grid solar inverter is working in Line, Standby or Fault mode,
charger source can be programmed as below:
Utility first
Utility will charge battery as first
priority.
Solar energy will charge battery only
when utility power is not available.
Solar first
Solar energy will charge battery as
first priority.
Utility will charge battery only when
solar energy is not available.
Solar and Utility
Solar energy and utility will both
charge battery.
Only Solar
Solar energy will be the only charger
source no matter utility is available or
not.
If this off grid solar inverter is working in Battery mode or Power saving
mode, only solar energy can charge battery. Solar energy will charge battery
if it's available and sufficient.
15
Alarm control
Alarm on (default)
Alarm off
16
Backlight control
Backlight on (default)
Backlight off
17
Beeps while primary
source is interrupted
Alarm on (default)
Alarm off
19
C.V. charging voltage.
If self-defined is selected
In program 5, this
program can be set up
Default 56.4V, 48.0V~58.4V Settable
20
Floating charging voltage.
If self-defined is selected in
program 5, this program
can be set up
Default 54.0V, 48.0V~58.4V Settable

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF 3000T HVM-G2 and is the answer not in the manual?

Growatt SPF 3000T HVM-G2 Specifications

General IconGeneral
ModelSPF 3000T HVM-G2
CategoryInverter
Rated Power3000W
Input Voltage230V AC
Output Voltage230V AC
Frequency50Hz/60Hz
Efficiency93%
Max. PV Array Power4000W
Max. Charging Current80A
Max Solar Input Voltage145V
Max Solar Input Power4000W
CommunicationRS232/USB
Operating Temperature-10°C to 50°C
Dimensions330 x 485 x 135 mm
Weight12 kg
ProtectionOverload, Short circuit, Over temperature

Related product manuals