Group 3.9.6: Temperature input fault 1
This parameter group is visible only with
an option board for temperature
measurement (OPT-BH) installed.
Code Parameter Min Max Unit Default ID Description
P3.9.6.1 Temperature signal 1 0 63 0 739
Selection of signals to use for alarm and
fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
B5 = Temperature Signal 6
Max value is taken of the chosen signals
and used for alarm/fault triggering.
Note: Only 6 first temperature inputs are
supported (counting boards from slot A to
slot E).
P3.9.6.2 Alarm limit 1 -30.0 200.0 °C 120.0 741
Temperature limit for trigging alarm.
Note: Only inputs chosen with parameter
P3.9.6.1 are compared.
P3.9.6.3 Fault limit 1 -30.0 200.0 °C 120.0 742
Temperature limit for trigging alarm.
Note: Only inputs chosen with parameter
P3.9.6.1 are compared.
P3.9.6.4 Fault limit response 1 0 3 2 740
0 = No response
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)