Group 3.9.6: Temperature input fault 2
This parameter group is visible only with
an option board for temperature
measurement (OPT-BH) installed.
Code Parameter Min Max Unit Default ID Description
P3.9.6.5 Temperature signal 2 0 63 0 763
Selection of signals to use for alarm and
fault triggering.
B0 = Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
B5 = Temperature Signal 6
Max value is taken of the chosen signals
and used for alarm/fault triggering.
Note: Only 6 first temperature inputs are
supported (counting boards from slot A to
slot E).
P3.9.6.6 Alarm limit 2 -30.0 200.0 °C 120.0 764
Temperature limit for triggering an alarm.
Note: Only inputs chosen with parameter
P3.9.6.5 are compared.
P3.9.6.7 Fault limit 2 -30.0 200.0 °C 120.0 765
Temperature limit for triggering an alarm.
Note: Only inputs chosen with parameter
P3.9.6.5 are compared.
P3.9.6.8 Fault limit response 2 0 3 2 766
0 = No response
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
Group 3.9.8: AI Low Protection
Code Parameter Min Max Unit Default ID Description
P3.9.8.1 AI Low Protection 0 2 2 767
This parameter defines if the AI Low protection is
enabled or disabled.
0 = Disabled
1 = Enabled in Run State
2 = Enabled in Run and Stop States
P3.9.8.2 AI Low Fault 0 5 0 700
Response when an analogue signal in use goes
below 50 % of the minimum signal range.
0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4 = Fault (Stop according to stop mode)
5 = Fault (Stop by coasting)