Pos. Description
1 Input Pressure
2 Input Pressure Monitor
3 Supervision Alarm Level
4 Supervision Fault Level
5 PID Setpoint
6 PID Setpoint
7 Supervision Fault Delay
Pos. Description
8 Supervision Fault Delay
9 PID Setpoint Reduction
10
Input Pressure Alarm
(Digital output signal)
11 Motor Running
12 Yes
13 No
Code Parameter Min Max Unit Default ID Description
P3.13.9.1 Superv. Enable 0 1 0 1685
0 = Disabled
1 = Enabled
Enables the Input Pressure
Supervision.
P3.13.9.2 Superv. Signal 0 13 Hz 0 1686
The source of input pressure
measurement signal:
0 = Analogue input 1
1 = Analogue input 2
2 = Analogue input 3
3 = Analogue input 4
4 = Analogue input 5
5 = Analogue input 6
6 = ProcessDataIn1 (0-100 %)
7 = ProcessDataIn2 (0-100 %)
8 = ProcessDataIn3 (0-100 %)
9 = ProcessDataIn4 (0-100 %)
10 = ProcessDataIn5 (0-100 %)
11 = ProcessDataIn6 (0-100 %)
12 = ProcessDataIn7 (0-100 %)
13 = ProcessDataIn8 (0-100 %)
P3.13.9.3 Superv. Unit Sel. 0 8 Varies 2 1687
Select unit for supervision. The
supervision signal (P3.13.9.2) can
be scaled to process units on the
panel.
P3.13.9.4 Superv. Unit Decimal 0 4 2 1688
Choose how many decimals to
show.
P3.13.9.5 Superv. Unit Min Varies Varies Varies Varies 1689 Unit min and max parameters are
the signal values corresponding to
e.g. 4 mA and 20 mA respectively
(scaled linearly between these).
P3.13.9.6 Superv. Unit Max Varies Varies Varies Varies 1690
P3.13.9.7 Superv. Alarm Level Varies Varies Varies Varies 1691
Alarm (Fault ID 1363) will be
launched if supervision signal stays
below the alarm level longer than
the time defined by parameter
3.13.9.9.