Code Parameter Min Max Unit Default ID Description
P3.13.9.8 Superv. Fault Level Varies Varies Varies Varies 1692
Fault (Fault ID 1409) will be
launched if supervision signal stays
below the fault level longer than the
time defined by parameter 3.13.9.9.
P3.13.9.9 Superv. Fault Delay 0.00 60.00 s 5.00 1693
Delay time to launch the Input
pressure supervision alarm or fault
if the supervision signal stays below
the alarm/fault level longer than
defined by this parameter.
P3.13.9.10 PID setpoint Reduct. 0.0 100.0 % 10.0 1694
Defines the rate of the PID
controller setpoint reduction when
the Input pressure supervision
alarm is active.
V3.13.9.11 InputPress. Monitor Varies Varies Varies Varies 1695
Monitoring value for selected Input
pressure supervision signal.
Scaling value according to
P3.13.9.4.
Group 3.13.10: Sleep - no demand detected
Code Parameter Min Max Unit Default ID Description
P3.13.10.1 Sleep No Demand
Detection Enable
0 1 0 1649
0 = No
1 = Yes
P3.13.10.2 SNDD Error Hysteresis 0
99999.
9
P3.13.
1.4
0.5 1658
P3.13.10.3 SNDD Frequency
Hysteresis
0.00
P3.3.1.
2
Hz 3.00 1663
P3.13.10.4 SNDD Supervision
Time
0 600 s 120 1668
P3.13.10.5 SNDD Actual Add 0.00
P3.13.
10.2
P3.13.
1.4
0.5 1669