EasyManua.ls Logo

Grundfos RSI - Page 119

Grundfos RSI
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Code Parameter Min Max Unit Default ID Description
P3.14.2.5 SP 1 Source 0 22 1 1643
0 = Not Used
1 = Keypad Setpoint 1
2 = Keypad Setpoint 2
3 = AI1
4 = AI2
5 = AI3
6 = AI4
7 = AI5
8 = AI6
9 = ProcessDataIn1
10 = ProcessDataIn2
11 = ProcessDataIn3
12 = ProcessDataIn4
13 = ProcessDataIn5
14 = ProcessDataIn6
15 = ProcessDataIn7
16 = ProcessDataIn8
17 = Temperature Input 1
18 = Temperature Input 2
19 = Temperature Input 3
20 = Temperature Input 4
21 = Temperature Input 5
22 = Temperature Input 6
AI's and ProcessDataIn are
handled as percent
(0.00-100.00 %) and scaled
according to Setpoint minimum
and maximum.
Note: ProcessDataIn signals
use 2 decimals.
P3.14.2.6 SP 1 Minimum -200.00 200.00 % 0.00 1644
Minimum value at analogue
signal minimum.
P3.14.2.7 SP 1 Maximum -200.00 200.00 % 100.00 1645
Maximum value at analogue
signal maximum.
P3.14.2.8 SP 2 Source 0 22 0 1646 See P3.14.2.5.
P3.14.2.9 SP 2 Minimum -200.00 200.00 % 0.00 1647
Minimum value at analogue
signal minimum.
P3.14.2.10 SP 2 Maximum -200.00 200.00 % 100.00 1648
Maximum value at analogue
signal maximum.
119
English (GB)

Other manuals for Grundfos RSI

Related product manuals