Group 3.14.3: Feedbacks
For more detailed information, see chapter Group
3.13: PID Controller.
Code Parameter Min Max Unit Default ID Description
P3.14.3.1 Function 1 9 1 1650
P3.14.3.2 Gain -1000.0 1000.0 % 100.0 1651
P3.14.3.3 FB 1 Source 0 25 1 1652 See P3.13.3.3.
P3.14.3.4 FB 1 Minimum -200.00 200.00 % 0.00 1653
Minimum value at analogue signal
minimum.
P3.14.3.5 FB 1 Maximum -200.00 200.00 % 100.00 1654
Maximum value at analogue signal
maximum.
P3.14.3.6 FB 2 Source 0 25 2 1655 See P3.13.3.6.
P3.14.3.7 FB 2 Minimum -200.00 200.00 % 0.00 1656
Minimum value at analogue signal
minimum.
P3.14.3.8 FB 2 Maximum -200.00 200.00 % 100.00 1657
Maximum value at analogue signal
maximum.
Group 3.14.4: Feedback Superv.
For more detailed information, see chapter Group
3.13: PID Controller.
Code Parameter Min Max Unit Default ID Description
P3.14.4.1 Enable Superv 0 1 0 1659
0 = Disabled
1 = Enabled
P3.14.4.2 Upper limit Varies Varies Varies Varies 1660
P3.14.4.3 Lower limit Varies Varies Varies Varies 1661
P3.14.4.4 Delay 0 30000 s 0 1662
If the desired value is not reached within
this time a fault or alarm is activated.
P3.14.4.5 Supervision Fault 0 3 2 757 See P3.9.1.2
Related information
8.1.14 Group 3.13: PID Controller
120