9.4.3 Code 3 (Fault ID 20 or 21, Earth fault)
Fault ID Fault name
20 Earth fault (hardware fault)
21 Earth fault (software fault)
Cause Remedy
Current measurement has detected that the motor
phase current sum is not zero.
• insulation failure in the cables or the motor
• Check the power cables and the motor.
9.4.4 Code 5 (Fault ID 40, Charging switch)
Cause Remedy
The charging switch is open, when the START
command is given.
• faulty operation
• component failure
• Reset the fault and restart.
• Contact the nearest distributor if the fault reoccurs.
9.4.5 Code 7 (Fault ID 60, Saturation)
Cause Remedy
Various causes:
• defective component
• brake resistor short circuit or overload
• It cannot be reset from keypad.
• Switch off power.
• Do not switch the power back on!
• Contact Grundfos.
• If this fault appears simultaneously with F1, check
the power cables and the motor.
9.4.6 Code 8 (Fault ID 600, System fault)
Cause Remedy
• Communication between control circuit and power
unit has failed.
• Reset the fault and restart.
• Contact the nearest distributor if the fault reoccurs.
9.4.7 Code 8 (Fault ID 601, System fault)
Cause Remedy
• Communication interference between control
circuit and power unit, but it is still working.
• Reset the fault and restart.
• Contact the nearest distributor if the fault reoccurs.
9.4.8 Code 8 (Fault ID 602, System fault)
Cause Remedy
• Watchdog has reset the CPU. • Reset the fault and restart.
• Contact the nearest distributor if the fault reoccurs.
9.4.9 Code 8 (Fault ID 603, System fault)
Cause Remedy
• Auxiliary power voltage in power unit is too low. • Reset the fault and restart.
• Contact the nearest distributor if the fault reoccurs.
169