Code Parameter Min Max Unit Default ID Description
P1.15 Identification 0 1 0 631
The identification run calculates or
measures the motor parameters that are
necessary for a good control of the
motor and speed.
0 = No action
1 = At standstill
2 = With rotation
Before you do the identification run, you
must set the motor nameplate parameters.
P1.16 Start function 0 1 0 505
0 = Ramping
1 = Flying start
P1.17 Stop function 0 1 0 506
0 = Coasting
1 = Ramping
P1.18 Automatic reset 0 1 0 731
0 = Disabled
1 = Enabled
P1.19 External fault 0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop according to stop mode)
3 = Fault (Stop by coasting)
P1.20 AI Low Fault 0 5 0 700
Response when an analogue signal in use
goes below 50 % of the minimum signal
range. 0 = No action
1 = Alarm
2 = Alarm, Preset Freq
3 = Alarm, Previous Freq
4= Fault (Stop according to stop mode)
5 = Fault (Stop by coasting)
P1.21
Rem.Ctrl. Place 0 1 0 172
Selection of remote control place (start/
stop). Can be used to change back to
remote control e.g. in case of a broken
panel.
0 = I/O control
1 = Fieldbus control
P1.22 I/O A Ref sel 1 9 5 117
Selection of ref source when control place
is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1 + AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P1.23 Keypad Ref sel 1 9 2 121
Selection of ref source when control place
is keypad:
See P1.22
28