Code Parameter Min Max Unit Default ID Description
P1.24 Fieldbus Ref sel 1 9 3 122
Selection of ref source when control place
is Fieldbus:
See P1.22
P1.25 AI1 signal range 0 1 0 379
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P1.26 AI2 signal range 0 1 1 390
0 = 0…10 V / 0…20 mA
1 = 2…10 V / 4…20 mA
P1.27 RO1 function 0 60 2 11001
Function selection for Basic R01:
0 = None
1 = Ready
2 = Run
3 = General fault
4 = General fault inverted
5 = General alarm
6 = Reversed
7 = At speed
8 = Thermistor fault
9 = Motor regulator active
10 = Start signal active
11 = Keypad control active
12 = I/O B control activated
13 = Limit supervision 1
14 = Limit supervision 2
15 = SinglePowerOn
16 = No function
17 = Preset speed active
18 = No function
19 = PID in Sleep mode
20 = PID soft fill active
21 = PID supervision limits
22 = Ext. PID superv. limits
23 = Input press. alarm/fault
24 = Frost prot. alarm/fault
25 - 30 = No function
31 = RTC time chnl 1 control
32 = RTC time chnl 2 control
33 = RTC time chnl 3 control
34 = FB ControlWord B13
35 = FB ControlWord B14
36 = FB ControlWord B15
37 = FB ProcessData1.B0
38 = FB ProcessData1.B1
39 = FB ProcessData1.B2
40 = Maintenance alarm
41 = Maintenance fault
42 = No function
43 = No function