Code Parameter Min Max Unit Default ID Description
44 = Block Out.1
45 = Block Out.2
46 = Block Out.3
47 = Block Out.4
48 = Block Out.5
49 = Block Out.6
50 = Block Out.7
51 = Block Out.8
52 = Block Out.9
53 = Block Out.10
54 = No function
55 = No function
56 = Auto-cleaning active
57 = Motor Switch Open
58 = TEST (Always Closed)
59 = No function
60 = DualSupply AC switch
P1.28 Basic R02 function 0 46 3 11004 See P1.27
P1.30 AO1 function 0 19 2 10050
0 = TEST 0 % (Not used)
1 = TEST 100 %
2 = Output freq (0 -fmax)
3 = Freq reference (0-fmax)
4 = Motor speed (0 - Motor nominal speed)
5 = Output current (0-I
nMotor
)
6 = Motor torque (0-T
nMotor
)
7 = Motor power (0-P
nMotor
)
8 = Motor voltage (0-U
nMotor
)
9 = DC link voltage (0-1000 V)
10 = PID1 output (0-100 %)
11 = Ext.PID output (0-100 %)
12 = ProcessDataIn1 (0-100 %)
13 = ProcessDataIn2 (0-100 %)
14 = ProcessDataIn3 (0-100 %)
15 = ProcessDataIn4 (0-100 %)
16 = ProcessDataIn5 (0-100 %)
17 = ProcessDataIn6 (0-100 %)
18 = ProcessDataIn7 (0-100 %)
19 = ProcessDataIn8 (0-100 %)
30
English (GB)