6.1.5.9 Copying parameters
This feature is available in graphical
keypad only.
The parameter copy function can be used to copy
parameters from one drive to another.
The parameters are first saved to the keypad, then
the keypad is detached and connected to another
drive. Finally the parameters are downloaded to the
new drive restoring them from the keypad.
Before any parameters can successfully be copied
from the keypad to the drive, the drive has to be
stopped before the parameters are uploaded.
1. First go into User settings menu and locate the
Parameter backup submenu. In the Parameter
backup submenu, there are three possible
functions to be selected:
2. Restore factory defaults will re-establish the
parameter settings originally made at the factory.
3. By selecting Save to keypad you can copy all
parameters to the keypad.
4. Restore from keypad will copy all parameters from
keypad to a drive.
STOP READY Keypad
Main Menu
Favourites
( 0 )
( 4 )
ID: M6
User settings
I/O and Hardware
( 8 )
STOP READY Keypad
Drive name
( 3 )
ID:
User settings
Application selection
HVAC
M6.5M6.5
Parameter backup
Drive
STOP READY Keypad
Restore from keypad
ID:
Restore factory defaults
M6.5M6.5.1
Save to keypad
Parameter backup
O K O
TM078670
Parameter copy
If the keypad is changed between drives of
different sizes, the copied values of these
parameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phi (P3.1.1.5)
Switching frequency (P3.1.2.3)
Motor current limit (P3.1.3.1)
Stall current limit (P3.9.3.2)
Stall time limit (P3.9.3.3)
Stall frequency (P3.9.3.4)
Maximum frequency (P3.3.1.2)