6.2.3 Parameters
Through this submenu, you can reach the application
parameter groups and parameters.
Related information
8. Parameters
6.2.4 Diagnostics
Under this menu, you can find Active faults, Reset
faults, Fault history, Total counters, Trip counters and
Software info.
Active faults
Menu Function Note
Active faults
When a fault/faults appear(s), the display
with the name of the fault starts to blink.
Press OK to return to the Diagnostics
menu. The Active faults submenu shows
the number of faults. Select the fault and
push OK to see the fault-time data.
The fault remains active until it is cleared
with the Reset button (push for 2 s) or with
a reset signal from the I/O terminal or
fieldbus or by choosing Reset faults (see
below).
The memory of active faults can store the
maximum of 10 faults in the order of
appearance.
Reset faults
Menu Function Note
Reset faults
In this menu you can reset faults. For
closer instructions, see chapter Faults.
Caution: Remove external Control signal
before resetting the fault to prevent
unintentional restart of the drive.
Fault history
Menu Function Note
Fault history
40 latest faults are stored in the Fault
history.
Entering the Fault history and clicking OK
on the selected fault shows the fault time
data (details).
Total counters
Code
Parameter Min Max Unit Default ID Description
V4.4.1 Energy counter Varies 2291
Amount of energy taken from supply
network. No reset.
V4.4.3
Operating time
(graphical keypad)
a d hh:min 2298 Control unit operating time
V4.4.7
Run time
(graphical keypad)
a d hh:min 2293 Motor running time
V4.4.11
Power on time
(graphical keypad)
a d hh:min 2294
Amount of time the power unit has been
powered so far. No reset.
V4.4.15
Start command
counter
2295
The number of times the power unit has
been started.
48