6.2.5 I/O and hardware
Various options-related settings are located in this
menu. Note that the values in this menu are raw
values i.e. not scaled by the application.
Basic I/O
Monitor here the statuses of inputs and outputs.
Code Parameter Min Max Unit Default ID Description
V5.1.1 Digital input 1 0 1 0 Status of digital input signal
V5.1.2 Digital input 2 0 1 0 Status of digital input signal
V5.1.3 Digital input 3 0 1 0 Status of digital input signal
V5.1.4 Digital input 4 0 1 0 Status of digital input signal
V5.1.5 Digital input 5 0 1 0 Status of digital input signal
V5.1.6 Digital input 6 0 1 0 Status of digital input signal
V5.1.7
Analogue input 1
mode
1 3 3
Shows the selected (with
jumper) mode for Analogue
input signal
1 = 0...20 mA
3 = 0...10 V
V5.1.8 Analogue input 1 0 100 % 0.00 Status of analogue input signal
V5.1.9
Analogue input 2
mode
1 3 3
Shows the selected (with
jumper) mode for Analogue
input signal
1 = 0...20 mA
3 = 0...10 V
V5.1.10 Analogue input 2 0 100 % 0.00 Status of analogue input signal
V5.1.11
Analogue output 1
mode
1 3 1
Shows the selected (with
jumper) mode for Analogue
output signal
1 = 0...20 mA
3 = 0...10 V
V5.1.12 Analogue output 1 0 100 % 0.00 Status of analogue output signal
V5.1.13 Relay output 1 0 1 0 Status of relay output signal
V5.1.14 Relay output 2 0 1 0 Status of relay output signal
V5.1.15 Relay output 3 0 1 0 Status of relay output signal
Option board slots
The parameters of this group depend on the option
board installed. If no option board is placed in slots D
or E, no parameters are visible.
As an option board is removed, info text 39 Device
removed will appear on the display.
50
English (GB)