Menu Function Note
Slot D
Settings Option board related settings.
Monitoring Monitor option board-related info.
Slot E
Settings Option board related settings.
Monitoring Monitor option board-related info.
Programming of digital and analogue inputs
The programming of inputs in the RSI is very flexible.
The available inputs on the standard and optional I/O
can be used for various functions according to the
operator's choice.
The available I/O can be expanded with optional
boards to be inserted in board slots D and E. More
information about the installation of optional boards
you will find in the RSI Installation manual.
Digital inputs
The applicable functions for digital inputs are
arranged as parameters in parameter group M3.5.1.
The value given to the parameter is a reference to the
digital input you choose to use for the function. The
list of functions that you can assign to the available
digital inputs is presented on Digital Inputs group.
Example
TM083253
Pos. Description
1 Graphical keypad
2 Parameter value (= Function)
3 Parameter value (= selected digital input)
Given the standard I/O board compilation on the RSI,
there are 6 digital inputs available (Slot A terminals 8,
9, 10, 14, 15 and 16). In the programming view, these
inputs are referred to as follows:
Input type
(Graphical keypad)
Slot Input # Explanation
DigIN A. 1
Digital input #1 (terminal 8) on board in Slot A
(standard I/O board).
DigIN A. 2
Digital input #2 (terminal 9) on board in Slot A
(standard I/O board).
DigIN A. 3
Digital input #3 (terminal 10) on board in Slot A
(standard I/O board).
51
English (GB)