Input type
(Graphical keypad)
Slot Input # Explanation
DigIN A. 4
Digital input #4 (terminal 14) on board in Slot A
(standard I/O board).
DigIN A. 5
Digital input #5 (terminal 15) on board in Slot A
(standard I/O board).
DigIN A. 6
Digital input #6 (terminal 16) on board in Slot A
(standard I/O board).
In the example below, the function External fault close
located in menu M3.5.1 as parameter P3.5.1.11, is by
default given the value DigIN SlotA.3 (graphical
keypad). This means that the function External fault
close is now controlled with a digital signal to digital
input DI3 (terminal 10).
This is what is shown in the parameter list.
Code Parameter Default ID Description
P3.5.1.11 External fault close DigIN SlotA.3 405
FALSE = OK
TRUE = External fault
Assume you need to change the selected input.
Instead of DI3 you wish to use DI6 (terminal 16) on
the standard I/O. Do as instructed here:
TM078678
Programming digital inputs with graphical keypad