Programming instructions
Graphical keypad
1. Select the parameter and push the Arrow right button.
2. You are now in the Edit mode as the slot value DigIN SlotA. is blinking and underlined. (Should you have
more digital inputs available in your I/O, for example, through inserted option boards in slots D or E, they can
also be selected here.).
3. Push the Arrow right button again to activate the terminal value 3.
4. Push the Arrow up button three times to change the terminal value to 6. Confirm with OK button.
5. Note: If the digital input DI6 was already used for some other function a message is displayed. You might
then want to change either of these selections.
Now, the function External fault close is controlled
with a digital signal to digital input DI6 (terminal 16).
The function is not assigned to any
terminal, or, the input is set to be always
FALSE, if its value is DigIN Slot0.1
(graphical keypad). This is the default
value of the majority of parameters in
group M3.5.1.
On the other hand, some inputs have been
by default set to be always TRUE. Their
value shows DigIN Slot0.2 (graphical
keypad).
Also Time Channels can be assigned to
digital inputs. See more information in
section Group 3.12: Timer functions.
53
English (GB)