Programming Instructions
Graphical keypad
1. Select the parameter and push the Arrow right button.
2. You are now in the Edit mode as the slot value AnIN SlotA. is blinking and underlined.
3. Push the Arrow up button once to change the slot value to AnIN SlotC. Confirm with OK button.
Descriptions of signal sources
Source Function
Slot0.#
Digital inputs:
A digital signal can be forced to a constant FALSE or TRUE state using this
functionality.
For example, some signals have been set to be always in TRUE state by
manufacturer, e.g parameter P3.5.1.15 (Run enable). Unless changed, Run
enable signal is always on.
# = 1: Always FALSE
# = 2-10: Always TRUE
Analogue inputs (used for testing purposes):
# = 1: Analogue input = 0 % signal strength
# = 2: Analogue input = 20 % signal strength
# = 3: Analogue input = 30 % signal strength
etc.
# = 10: Analogue input = 100 % signal strength
SlotA.# Number (#) corresponds to digital input in slot A(Standard terminals).
SlotD.# Number (#) corresponds to digital input in slot D.
SlotE.# Number (#) corresponds to digital input in slot E.
TimeChannel.#
Number (#) corresponds to:
1 = Time Channel1
2 = Time Channel2
3 = Time Channel3
Fieldbus CW.# Number (#) refers to Control Word bit number.
FieldbusPD.# Number (#) refers to Process Data 1 bit number.
Default assignments of digital and analogue
inputs in RSI
Digital and analogue inputs are assigned certain
functions by the factory. In this application, the default
assignments are:
Input Terminal(s) Reference Assigned function Parameter code
DI1 8 A.1 Control signal 1 A P3.5.1.1
DI2 9 A.2 Control signal 2 A P3.5.1.2
DI3 10 A.3 External fault close P3.5.1.11
DI4 14 A.4 Preset Freq Sel0 P3.5.1.21
DI5 15 A.5 Preset Freq Sel1 P3.5.1.22