Input Terminal(s) Reference Assigned function Parameter code
DI6 16 A.6 External fault close P3.5.1.13
AI1 2/3 A.1 AI1 signal selection P3.5.2.1.1
AI2 4/5 A.2 AI2 signal selection P3.5.2.2.1
Real time clock
Code Parameter Min Max Unit Default ID Description
V5.5.1 Battery state 1 3 2 2205
Status of battery.
1 = Not installed
2 = Installed
3 = Change battery
P5.5.2 Time hh:mm:ss 2201 Current time of day
P5.5.3 Date dd.mm. 2202 Current date
P5.5.4 Year yyyy 2203 Current year
P5.5.5 Daylight saving 1 4 1 2204
Daylight saving rule
1 = Off
2 = EU; Starts on last
Sunday in March, ends last
Sunday in October
3 = US; Start on 2nd Sunday
in March, ends on 1st
Sunday in November
4 = Russia (permanent)
Power unit settings
Fan control
The fan operates in speed-controlled mode. The
speed is controlled according to the drive's internal
logic that receives data from temperature
measurements.
Code Parameter Min Max Unit Default ID Description
V5.6.1.3 Fan stop 0 1 1 826
If enabled, the fan will stop in
5 minutes when the drive is
in Ready state.
0 = Disabled
1 = Enabled
Brake chopper
Code Parameter Min Max Unit Default ID Description
V5.6.2.1 Brake chopper mode 0 3 0
0 = Disabled
1 = Enabled (Run)
2 = Enabled (Run & Stop)
3 = Enabled (Run, no testing)
56
English (GB)