Sine filter
Code Parameter Min Max Unit Default ID Description
V5.6.4.1 Sine filter 0 1 0
0 = Disabled
1 = Enabled
Keypad
Code Parameter Min Max Unit Default ID Description
P5.7.1 Timeout time 0 60 min 0
Time after which the display
returns to page defined with
parameter P5.7.2.
0 = Not used
P5.7.2 Default page 0 4 0
The page the keypad shows
when the drive is powered on
or when the time defined with
P5.7.1 has expired. If the
value is set to 0 the page last
visited is shown.
0 = None
1 = Enter menu index
2 = Main menu
3 = Control page
4 = Multimonitor
P5.7.3 Menu index
Set menu index for desired
page and activate with
parameter P5.7.2 = 1.
P5.7.4 Contrast 30 70 % 50
Set contrast of the display
(30...70 %).
P5.7.5 Backlight time 0 60 min 5
Set the time until the
backlight of the display turns
off (0...60 min). If set to 0 s,
backlight is always on.