Code Parameter Min Max Unit Default ID Description
P3.3.1.5 I/O A Ref sel 1 9 5 117
Selection of ref source when control
place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.6 I/O B Ref sel 1 9 9 131
Selection of ref source when control
place is I/O B. See above.
Note: I/O B control place can only
be forced active with digital input
(P3.5.1.7).
P3.3.1.7 Keypad Ref Sel 1 9 2 121
Selection of ref source when control
place is keypad:
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID reference
8 = Motor potentiometer
9 = Max Power
P3.3.1.8 Keypad Reference 0.00 P3.3.1.2 Hz 0.00 184
The frequency reference can be
adjusted on the keypad with this
parameter.
81