Code Parameter Min Max Unit Default ID Description
P3.4.3.2 StartMagnTime 0,00 600,00 s 0,00 516
This parameter defines the time for how long
DC current is fed to motor before acceleration
starts.
Group 3.4.3: DC brake
Code Parameter Min Max Unit Default ID Description
P3.4.4.1 DC Brake Current Varies Varies A Varies 507
Defines the current injected into the motor
during DC-braking.
0 = Disabled
P3.4.4.2 DC BrakeTime 0,00 600,00 s 0,00 508
Determines if braking is ON or OFF and the
braking time of the DC-brake when the
motor is stopping.
P3.4.4.3 DC Start Freq 0,10 10,00 Hz 1,50 515
The output frequency at which the DC-
braking is applied.
Group 3.4.5: Flux Braking
Code Parameter Min Max Unit Default ID Description
P3.4.5.1 Flux Braking 0 1 0 520
0 = Disabled
1 = Enabled
P3.4.5.2 Braking Current 0 Varies A Varies 519 Defines the current level for flux braking.