8.1.6 Group 3.5: I/O Config
Default assignments of programmable inputs
The table below presents the default assignments of
programmable digital and analogue inputs in RSI.
Input Terminal(s) Reference Assigned function Parameter code
DI1 8 A.1 Ctrl signal 1 A P3.5.1.1
DI2 9 A.2 Ctrl signal 2 A P3.5.1.2
DI3 10 A.3 External fault close P3.5.1.11
DI4 14 A.4 Preset frequency selection 0 P3.5.1.21
DI5 15 A.5 Preset frequency selection 1 P3.5.1.22
DI6 16 A.6 External fault close P3.5.1.13
AI1 2/3 A.1 AI1 signal selection P3.5.2.1.1
AI2 4/5 A.2 AI2 signal selection P3.5.2.2.1
Group 3.5.1: Digital inputs
Digital inputs are very flexible to use. Parameters are
functions that are connected to the required digital
input terminal (see chapter User interfaces). The
digital inputs are represented as, for example, DigIN
Slot A.2, meaning the second input on slot A.
It is also possible to connect the digital inputs to time
channels which are also represented as terminals.
The statuses of digital inputs and the
digital output can be monitored in the
Multi-monitoring view.
Code Parameter Default ID Description
P3.5.1.1 Ctrl signal 1 A DigIN SlotA.1 403 Ctrl signal 1 when control place is I/O A (FWD)
P3.5.1.2 Ctrl signal 2 A DigIN SlotA.2 404 Ctrl signal 2 when control place is I/O A (REV)
P3.5.1.4 Ctrl signal 1 B DigIN Slot0.1 423 Start signal 1 when control place is I/O B
P3.5.1.5 Ctrl signal 2 B DigIN Slot0.1 424 Start signal 2 when control place is I/O B
P3.5.1.7 I/O B Ctrl Force DigIN Slot0.1 425 TRUE = Force the control place to I/O B
P3.5.1.8 I/O B Ref Force DigIN Slot0.1 343
TRUE = Used frequency reference is specified
by I/O reference B parameter (P3.3.1.6).
P3.5.1.9 Fieldbus Ctrl Force DigIN Slot0.1 411 Force control to fieldbus
P3.5.1.10 Keypad Ctrl Force DigIN Slot0.1 410 Force control to keypad
P3.5.1.11 Ext Fault Close DigIN SlotA.3 405
FALSE = OK
TRUE = External fault
P3.5.1.12 Ext Fault Open DigIN Slot0.2 406
FALSE = External fault
TRUE = OK
P3.5.1.13 Fault Reset Close DigIN SlotA.6 414 Resets all active faults when TRUE
P3.5.1.14 Fault Reset Open DigIN Slot0.1 213 Resets all active faults when FALSE
P3.5.1.15 Run Enable DigIN Slot0.2 407 Must be on to set drive in Ready state
P3.5.1.16 Run Interlock 1 DigIN Slot0.2 1041
Drive may be ready but start is blocked as long
as interlock is on (Damper interlock).
P3.5.1.17 Run Interlock 2 DigIN Slot0.2 1042 As above.