Code Parameter Default ID Description
P3.5.1.21 Preset Freq Sel0 DigIN SlotA.4 419
Binary selector for Preset speeds (0-7). See
Group 3.3.3: Preset Freqs.
P3.5.1.22 Preset Freq Sel1 DigIN SlotA.5 420
Binary selector for Preset speeds (0-7). See
Group 3.3.3: Preset Freqs.
P3.5.1.23 Preset Freq Sel2 DigIN Slot0.1 421
Binary selector for Preset speeds (0-7). See
Group 3.3.3: Preset Freqs.
P3.5.1.24 MotPot UP DigIN Slot0.1 418
FALSE = Not active
TRUE = Active (Motor potentiometer reference
INCREASES until the contact is opened)
P3.5.1.25 MotPot DOWN DigIN Slot0.1 417
FALSE = Not active
TRUE = Active (Motor potentiometer reference
DECREASES until the contact is opened)
P3.5.1.27 Timer 1 DigIN Slot0.1 447
Rising edge starts Timer 1 programmed in
Group 3.12: Timer functions parameter group
P3.5.1.28 Timer 2 DigIN Slot0.1 448 See above
P3.5.1.29 Timer 3 DigIN Slot0.1 449 See above
P3.5.1.30 PID SP Boost DigIN Slot0.1 1046
FALSE = No boost
TRUE = Boost
P3.5.1.31 PID SP Selection DigIN Slot0.1 1047
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.32 ExtPID StartSignal DigIN Slot0.2 1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect if the
external PID-controller is not enabled in Group
3.14: ExtPID Controller.
P3.5.1.33 ExtPID SP Select DigIN Slot0.1 1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.40 MainCounter1Reset DigIN Slot0.1 490
Reset the counter from digital input.
TRUE = Reset
P3.5.1.48 AutoClean Activ. DigIN Slot0.1 1715
Start the Auto-cleaning sequence.
The sequence will be aborted if activation
signal is removed before the sequence has
been completed.
Note: The drive will start if the input is
activated.
P3.5.1.49 Param. Set 1/2 Sel. DigIN Slot0.1 496
Parameter set 1/2 selection.
Open= Parameter Set 1
Closed= Parameter Set 2
P3.5.1.50 User Defined Fault 1 DigIN Slot0.1 15523
Digital input selection for activating User
Defined Fault (1 or 2).
Open = No operation
Closed = Fault Activated
P3.5.1.51 User Defined Fault 2 DigIN Slot0.1 15524
Digital input selection for activating User
Defined Fault (1 or 2).
Open= No operation
Closed= Fault Activated
87