EasyManua.ls Logo

Grundfos TP 32-40 - Motor Technology; TPE Pump Motor Description; TPE Motor Electrical Data

Grundfos TP 32-40
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Motors for TPE pumps
TPE E-circulators
11
21
11. Motors for TPE pumps
Motor
The motor fitted on TPE pumps is a totally enclosed,
fan-cooled standard motor with main dimensions and
electrical tolerances to NEMA standards.
Relative humidity: Max. 95 %
Enclosure class: TEFC
Insulation class: F, to IEC 85
Ambient temperature: Max. +104 °F
Motor range
Motor protection
Single-phase motors have integrated, interconnected
thermal switches.
Electrical data
2 pole (3600 rpm)
4 pole (1800 rpm)
* The values apply to the combined efficiency of the motor and variable frequency drive.
hp
Electronic speed controlled motors
2-pole/1 ph 4-pole/1 ph
0.34
MLE
MLE
0.50
0.75
1.0
1.5
MLE is Grundfos motor brands.
The grey-shaded areas indicate non-available motors.
Hp Voltage Ph
NEMA
frame
Service
factor
Full load
eff [%] *
Ins.
class
Full
load
amps
Power
factor
Min/max
speed
[rpm]
0.5 208-230 1 56C 1.0 71.0 F 2.8 - 2.5 0.96 360-3400
0.75 208-230 1 56C 1.0 74.0 F 3.9 - 3.5 0.97 360-3400
1 208-230 1 56C 1.0 76.0 F 5.2 - 4.7 0.97 360-3400
1.5 208-230 1 56C 1.0 77.0 F 7.5 - 6.8 0.97 360-3400
Hp Voltage Ph
NEMA
frame
Service
factor
Full load
eff [%] *
Ins.
class
Full
load
amps
Power
factor
Min/max
speed
[rpm]
0.33 208-230 1 56C 1.0 67.0 F 2 - 1.9 0.94 180-1690
0.5 208-230 1 56C 1.0 70.0 F 2.8 - 2.5 0.96 180-1690
0.75 208-230 1 56C 1.0 72.0 F 4 - 3.70 0.96 180-1690
1 208-230 1 56C 1.0 73.0 F 5.4 - 4.9 0.97 180-1690
E-circulator.book Page 21 Friday, October 7, 2011 4:01 PM